Image File Server Requirements (5U Rack Mounted)

(Not needed for a data-only system)

System Size Small Medium Large
Processor: Single Intel® Quad Core Xeon Processor E5410 2x6MB Cache, 2.33GHz, 1333MHz FSB Single Intel® Quad Core Xeon Processor E5430 2x6MB Cache, 2.66GHz, 1333MHz FSB Single Intel® Quad Core Xeon Processor E5440 2x6MB Cache, 2.83GHz, 1333MHz FSB
Bus Type: PCI-E PCI-E PCI-E
Memory (RAM): 1 GB Fully Buffered DIMM'S at 667MHz Single Ranked 2 GB Fully Buffered DIMM'S at 667MHz Single Ranked 4 GB Fully Buffered DIMM'S at 667MHz Dual Ranked
Hard Disk: 4x146 GB Hot Swap drives with SAS interface (includes online spare). Drives should have < 10ms access time at 10 000 RPM. Effective disk space is 292 GB. 6x300 GB Hot Swap drives with SAS interface (includes online spare). Drives should have < 10ms access time at 10 000 RPM. Effective disk space is 1.2 TB. 8x300 GB Hot Swap drives with SAS interface (includes online spare). Drives should have < 10ms access time at 10 000 RPM. Effective disk space is 1.8 TB.
Drive Controller: Dual channel SAS 3.0Gb/s RAID controller with ≥ 256 MB cache. Configured for hardware RAID 5 fault tolerance and read/write cache enabled (software NOS controlled RAID 5 not recommended). CD and LTO tape should operate from channel 2 of controller or a separate controller. Dual channel SAS 3.0Gb/s RAID controller with ≥ 256 MB cache. Configured for hardware RAID 5 fault tolerance and read/write cache enabled (software NOS controlled RAID 5 not recommended). CD should operate from channel 2 of controller. External LTO4-120 operate with a separate SAS controller. Dual channel SAS 3.0Gb/s RAID controller with ≥ 256 MB cache. Configured for hardware RAID 5 fault tolerance and read/write cache enabled (software NOS controlled RAID 5 not recommended). CD should operate from channel 2 of controller. External LTO4-120 operate with a separate SAS controller.
Floppy Disk: 3.5" drive, 1.44 MB 3.5" drive, 1.44 MB 3.5" drive, 1.44 MB
Optical Drive: Multisession 24X CD-RW and DVD-ROM combo Drive Multisession 24X CD-RW and DVD-ROM combo Drive Multisession 24X CD-RW and DVD-ROM combo Drive
Backup Tape: LTO-3 400/800 GB internal tape drive BrightStor™ ARCserve® 11.5 or later. External 2U LTO-4-120 tape library BrightStor™ ARCserve® 11.5 or later and ARCserve® 11.5 tape library software required. External 2U LTO-4-120 tape library BrightStor™ ARCserve® 11.5 or later and ARCserve® 11.5 tape library software required.
Network Interface: 1 LOM 10/100/1000 Mbps, compatible with the network operating system and cabling. 1 LOM 10/100/1000 Mbps, compatible with the network operating system and cabling. 1 LOM 10/100/1000 Mbps, compatible with the network operating system and cabling.
Redundancy: PSU and Fans PSU and Fans PSU and Fans
Ports: 1 serial, minimum 2 USB 1 serial, minimum 2 USB 1 serial, minimum 2 USB
Network Operating System: VARiS Vision: Microsoft® Windows® 2000 Server Standard, Service Pack 4 (Server 25 client access license or sufficient seat licenses)
ARIA: Microsoft® Windows® Server 2003 R2 (Standard or Enterprise) with Service Pack 2 (25 client access license or sufficient seat licenses)
VARiS Vision: Microsoft® Windows® 2000 Server Standard, Service Pack 4 (Server 25 client access license or sufficient seat licenses)
ARIA: Microsoft® Windows® Server 2003 R2 (Standard or Enterprise) with Service Pack 2 (25 client access license or sufficient seat licenses)
VARiS Vision: Microsoft® Windows® 2000 Server Standard, Service Pack 4 (Server 25 client access license or sufficient seat licenses)
ARIA: Microsoft® Windows® Server 2003 R2 (Standard or Enterprise) with Service Pack 2 (25 client access license or sufficient seat licenses)
File System NTFS NTFS NTFS
Microsoft® OS Architecture 32-bit (not 64-bit) 32-bit (not 64-bit) 32-bit (not 64-bit)
Microsoft® .NET Framework 1.1 and 2.0 (not 3.0) 1.1and 2.0 (not 3.0) 1.1 and 2.0 (not 3.0)
42U Half Height Rack Mounted systems come with the following components (see notes below):
  • Cables for Keyboard and Video
  • NEMA standard powerstrip
  • 1U 8-port keyboard/monitor KVM switch box
  • 1U keyboard/trackball and monitor console
  • 2U 3000VA Uninterruptable Power Supply (UPS)
  • 24-port patch panel (CAT5E)

NOTES:

  1. Hardware used should be approved based on the current Microsoft® Windows® Catalog Listing.
  2. In addition to this Image Fileserver, the following database server is required for use with Image-based products and would be installed in the same rack.
  3. 1 Gbps network recommended for maximum speed and performance.
  4. In addition to this image server, the following T-Box server is required and would be installed in the same rack.
  5. Specifications subject to change without notice as newer computer models become available.
  6. Specifications subject to change without notice as newer computer models become available.

 

Contact Varian Oncology

Varian Oncology Headquarters
Tel: 1.650.424.5700
Fax: 1.650.493.5637
E-Mail: ca@varian.com

Events

© 1999-2008 Varian Medical Systems, Inc. All rights reserved.
Production of any of the material contained herein in any format or media without the express written permission of Varian Medical Systems is prohibited.

North America